Add and connect devices in plant control
Scope
This guide puts the devices of a site on the Plant Control Diagram, with one line for each cable. See How plant control works.
Location
- Path: My Devices, Plant Control System, then the Diagram tab.
- Edit mode: the menu at the top left of the canvas, then Edit.
Permissions
- Add, connect, change and remove devices:
Editor,InstallerorFull control.
Step 1: Device Points
The system adds a battery and a hybrid inverter on the logger with Enabled set to Enabled. It adds other devices with Enabled set to Disabled.
To add a grid, load, generator, PV meter or switch point:
- In the Diagram menu, click Add device.
- Select the Device Type.
- Type a Device Serial that no other point of that type uses.
- Click Save.
Set Rated Power and Max Limit before you set a new grid or generator point to Enabled. Both start at 0, and a Max Limit of 0 permits no import.
Step 2: Point Settings
- In the Diagram menu, click Edit.
- Double-click the point.
- On the Basic tab, set Enabled: to Enabled.
- On a grid or generator point, set Rated Power: to the rating of the connection.
- On the Max Limit tab, set the Default rule. See Build a rule list.
- Click Save.
Step 3: Lines
- Drag from a dot on one device to a dot on the other device of the cable.
Connect each grid, generator and load point to the meter or inverter that measures it.
- Energy meter: input on the left. Connect the supply side to the input, or the reading changes sign.
- Hybrid inverter: grid on the left, load on the right.
- AC Control ATS: inputs on the left, input 1 at the top. Output on the right.
The AC Loops tab then shows each loop that the lines make, with its devices.
Step 4: Battery Link
- Find the battery serial on the Diagram, for example hv_1 (high voltage, cluster 1).
- On each inverter or charger of that battery, set Storage Cluster ID: to the cluster number.
- Click Save.
Step 5: Switch Position
- On the Basic tab of the switch, set Input ID: to the logger input that reports the position.
- Set Input Polarity:. Straight reads the switch closed while the input is on.
- On an AC Control Switch, set Output ID: to the output that operates it.
- Click Save.
Troubleshooting
- Device not added: Device [...] already exist: a point of that type uses that Device Serial. Type a different serial, then click Save again.
- Device link: [...] already exist!: the two dots have a line.
- can not locate storage data cluster ID: no battery of that voltage has that Storage Cluster ID.
Tips and Gotchas
- To keep moved devices, click the save icon at the top right of the canvas.
To stop the control of a device, set Enabled to Disabled. Remove Device, on the Advanced tab, deletes the settings and rules of the device permanently.