Winline Charger Cluster - battery charger
Description
- Device class: a group of Winline UXR 40 kW DC charging modules on one CAN bus, controlled as one battery charger
- Brand: Winline
- Name in My Devices: Winline Charger Cluster
- Name in the Add Device wizard: Charger Cluster, under Winline
- Module models: UXR100040 and UXR100040B
- Module output: 100 Vdc to 1000 Vdc, 0 A to 133.3 A, 40 kW
- Module AC input, UXR100040: 3 phase and PE, 285 Vac to 475 Vac
- Module AC input, UXR100040B: 3 phase and PE, 260 Vac to 530 Vac
- Cluster: one cluster for each LoggerV CAN port, with all the modules on that port
- Module names: UXR_ followed by the port and the module address, for example UXR_c1_0 for address 0 on CAN-1
- Battery: the charge limits come from a Solar MD Li-ion H8 Series high-voltage battery cluster; see Battery Communication
LoggerV Connection
| Interface | Protocol | Port or baud rate |
|---|---|---|
| CAN | Winline UXR CAN protocol | 125 kbps |
- No address in the wizard: CAN, the modules announce themselves
- LoggerV hardware: 2.12, 2.13 and 2.20
Plant Control Functions
- Charger fed from AC: charge power only. A discharge request sets the charge power to 0 W.
- Power to current: the LoggerV divides the setpoint by the output voltage and shares the current equally over the online modules
- Current ramp: up by Cluster Step Current at each Cluster Step Delay. A decrease is applied in one step. A Cluster Step Current of 0 switches off the ramp.
- Off at 0 W: the modules stay on at 0 A for Power Off Hold, then switch off. Power Off Hold is 15000 ms by default, 0 to 600000 ms.
- Not implemented: start and stop mode commands, frequency response, reactive power
The LoggerV obeys plant control only while Plant Control Enabled is set to Enable.
While Plant Control Enabled is set to Enable, the LoggerV does not apply the battery charge limits. Plant control alone sets the charge power.
Recorded Data
| Field | Unit |
|---|---|
| Online Modules | modules |
| Offline Modules | modules |
| Target Current | A |
| Target Power | W |
| Output Current | A |
| Output Power | W |
| Output Voltage | V |
| AC Input Power | W |
| DC-DC Temp Max, Min, Avg | °C |
| PFC Temp Max, Min, Avg | °C |
| Ambient Temp Max, Min, Avg | °C |
- Temperatures: the highest, lowest and average of the online modules. No online module records no value.
- Record Power Data: no effect. The platform records the fields above with the setting on or off.
Reference Documents
These open in the myPower24 library. Sign in to read them.
- Winline UXR100040 charging module user manual V2.3
- Winline UXR100040B charging module user manual V1.3
- Solar MD and Winline UXR charger CAN wiring guide v2
Wiring
The Add-Device wizard makes the connection diagrams; see How to add a device in myPower24.
| Signal | LoggerV RJ45 (CAN-1 or CAN-2) | Module adapter plate (J1 or J2) |
|---|---|---|
| CAN High | Pin 4 | Right pin |
| CAN Low | Pin 5 | Left pin |
| Ground | Pin 2 | Not connected |
- AC input connector: 1 L3, 2 L2, 3 L1, 4 PE
- DC output connector: 1 and 2 DC+, 3 and 4 DC-, 5 CAN High, 6 CAN Low
- Bus shape: one line from module to module, not a star
- Termination: 120 Ω at the first and the last device. With the power off, CAN High to CAN Low is 60 Ω.
- LoggerV termination: built-in 120 Ω resistor with an ON/OFF switch
- Module termination: jumper J7. Pins 1 and 2 connect the resistor. Pins 2 and 3 disconnect it.
Setup
- Connect the cable as the generated diagram shows.
- Set the LoggerV resistor to ON. Put the J7 jumper on pins 1 and 2 on the last module only.
- Set the module address with the front panel buttons. Hold ▲ or ▼ for 2.5 seconds, change the value, then hold for 2.5 seconds to save.
- Set the address of the first module on the CAN line from the LoggerV to 0.
- Set each next module to the next address: 1, 2, 3, 4, 5, 6, 7, 8, 9, a, b, c, d, e, f. Do not skip an address.
- Add the device on the LoggerV; see How to add a device in myPower24. Select Charger Cluster under Winline, then the CAN port.
- Open Cluster Control > Operational Settings. Set Cluster Max Voltage Setpoint, from 200 to 1000 V.
- Set Cluster Voltage Setpoint, not more than Cluster Max Voltage Setpoint.
- Set Cluster On/Off to Enable.
- Open Cluster Data. Make sure that Online Units is the number of modules and Offline Units is 0.
The module address is hexadecimal. Address a is the 11th module and address f is the 16th module. Two modules must not have the same address.
Battery Communication
The LoggerV limits the chargers with the charge control values of a Solar MD Li-ion H8 Series battery cluster on the same LoggerV.
- Setting: Cluster Control > Advanced Settings > Battery Controlled, Enable by default
- Battery Cluster ID: the Cluster ID on the H8 device page, 1 by default
- Limits: the cluster current and voltage do not go above the battery charge control values
- No battery cluster or no battery online: the cluster charges at 0 A and shows an alert
- Status: Cluster Data > Charge Control Status
Set Battery Cluster ID before you switch the cluster on. A wrong ID stops the charge or applies the limits of a different battery.
Device Page
- Device Info: serial number, rated power, manufacturer, rated current
- Cluster Data: on/off, ramp, control mode, Online Units, Offline Units, actual and target values, charge control
- Module Data: one tab for each module, with its alerts, status, temperatures, DC and AC values. Red is a fault, orange a warning, blue information.
- Cluster Config: Working Altitude, Max Voltage Setpoint, Over Voltage Reset, Over Voltage Protection, SC Reset, Input Mode, data recording
- Cluster Control: cluster on/off, voltage, power and current setpoints, current stepping, Plant Control Enabled, battery control
- Healthy link: Online Units is the number of modules, Offline Units is 0, and each module tab shows Connected
- Offline Units: includes each removed module. The LoggerV remembers each module that it found.
Maintenance
- Open the AC input breaker of the module.
- Remove the two front panel screws.
- Pull the module out by its handle.
- Set the new module to the address of the old module.
- Push the new module fully into the slot and install the two screws.
- Close the AC input breaker.
- Make sure that the module tab on Module Data shows Connected.
Open the AC breaker before you remove a module. The module housing can be hot after operation.
Troubleshooting
Front Panel Error Codes
Read the model on the module label first. The two models use the same codes for different faults.
| Fault | UXR100040 | UXR100040B |
|---|---|---|
| AC voltage or phase loss | E03 | E01 |
| Overtemperature | E02 | E04, E08 |
| Output over voltage | E06 | E02 |
| Output short circuit | E05 | E05 |
| Fan fault | E08 | E06 |
| Address conflict | E07 | E10 |
| Output under voltage | E01 | none |
| Current sharing | E09 | none |
| Module damaged | none | E03, E07, E09 |
- AC voltage or phase loss: measure the AC input. Examine the cables.
- Overtemperature: clean the air inlet and outlet. Examine the cabinet fans.
- Output over voltage: examine the voltage setpoint. Remove and install the module to reset it.
- Output short circuit: find and repair the short circuit between DC+ and DC-.
- Fan fault: examine the fan cable. If the fault stays, send the module to Winline.
- Address conflict: set a different address on each module.
- Output under voltage: the module starts again after 5 seconds. Examine the load.
- Current sharing: examine the DC output connection to the load.
- Module damaged: send the module to Winline.
LoggerV Messages
- "Value may not be bigger than Cluster MAX Voltage": set Cluster Max Voltage Setpoint first
- "Not Allowed, Plant Control Enabled": plant control sets the power. Set Plant Control Enabled to Disable first.
- "Not Allowed, Power Control mode enabled": use Cluster Power Setpoint, or set Power Control Mode to Disable
- "Power Control NOT mode enabled": set Power Control Mode to Enable first
- "Could not find cluster with ID: …": no H8 battery cluster has that Cluster ID. Read it on the H8 device page.
- "Could not attach to interface.": another device uses that CAN port
- "Timeout. Please check logger connection": make sure that the LoggerV is online
Alerts
- "No Cluster Found for ID: … - Using Fallback Current of 0A": correct Battery Cluster ID, or examine the battery link
- "No batteries online in cluster - Using Fallback Current of 0A": the cluster charges at 0 A until a battery comes online
- "Charger unit … has … alerts!": open the module tab on Module Data
- "Failed to read data from: … Address: …": examine the CAN cable and the termination
- "Invalid Com ID: […]. ID should start from 0, and highest ID can be […] for this cluster with […] modules.": set the addresses from 0 with no gaps
- "CAN communication fault": examine the CAN cable and the termination. The module stops its output after 10 seconds without communication.
- "DCDC power off": correct when Cluster On/Off is Disable or after Power Off Hold
Permissions
- Viewer: the device page and the recorded data, read only
- Editor, Installer or Full control: every setting on Cluster Config and Cluster Control
- Module protection settings: Over Voltage Protection, Over Voltage Reset, SC Reset and Max Voltage Setpoint have no role gate. Editor access is sufficient to change them.
- Advanced and OEM roles: no more access on this device
A higher level includes all lower-level access.